The MC608 A/B converter has been designed with the purpose of meeting all the requirements of modern water management systems. The converters MC608 A/B are compatible with all EUROMAG INTERNATIONAL sensors.
General Features
| Power supply MC608A |
90...264 Vac 12/24 Vac/dc |
| Power supply MC608B |
Battery powered supply or 12/24 Vac/dc Expected life T=0 / 50°C ( 32 / 122 °F) Internal battery pack » 3-6 anni Internal and external battery pack » 6-10 anni |
| Display |
Graphic LCD 128x64 pixels, 50x25mm visual area. Backlit white colour, programmable backlighting. Simultaneous display of a counter + instant variable + status flags. Counters with 8 mm high charachters for reliable and easy reading.Programmable display content.
|
| Keyboard |
yes |
| Programming mode |
menù |
| Signals in output |
- Active analogue output 4-20 mA (requiring external 24 V DC power);
- Digital output1000 Hz duty cycle max 50% for instant load, positive only, positive and negative;
- Programmable digital output for:
- Maximum pulses output for 1000 Hz duty cycle max 50% for negative load
- Negative load indication;
- Cumulative alarm
- Digital output in active frequency 0-10 kHz (requiring external 24 VDC power);
All outputs are optoisolated. Pulse outputs with a maximum capacity of ±35 V DC 50 mA. |
| Serial Communication |
- IrDA interface for communicating with laptop or hand held communicator, and dedicated SW for programming, displaying and downloading data.
- MODBUS RTU interface on RS 485.
|
| Temperature range |
Process » -10°C a 70°C Ambient » -20°C a 60°C Storage » -30°C a 70°C |
| Accuracy |
0.2% of the read value minimum2.0 mm/s |
| Repeatability |
0.1% of the read value minimum 2.0 mm/s |
| Calibration |
Standard Generic use in water » 0.4 % High performance application » 0.2% |
| Measuring stabilization time |
3s |
| Degree of protection |
IP 67/68 |
| Sampling frequency |
Programmable 5, 3, 1, 1/15, 1/30, 1/60, 1/120, 1/240, 1/480 Hz. |
|